You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
When you use the LR off plug that means Ir = 1 and Tr = very far from standard times delay (near infinity).
There is a direct relationship between load shedding and the long time delay protection so for this reason the load shedding will remain off too.
You can replace it with the 3 alarms called Ia max, Ib max and Ic max, each alarm have to work in relationship with 3 contacts of the M6C.
The power shedding feature is not affected if you install a LT Off Rating Plug