Issue:
What could cause the errors: "Invalid Read Reply" and "Specified Address Invalid" on the Magelis when communicating to the Siemens S7-1200 ethernet driver?
Product Line:
S7-1211C, S7-1212C, S7-1214C, S7-1215C, S7 ethernet
Resolution:
Protection
From TIA (Siemens programming software), Select the CPU project in the left pane and press Alt-Enter (or in the contextual menu select “Properties…”)
In the item Protection, select “Full access” and Check “Permit access with PUT/GET communications from remote partner” as in figure below.

Information was taken from: http://snap7.sourceforge.net/snap7_client.html 2-25-2016
What could cause the errors: "Invalid Read Reply" and "Specified Address Invalid" on the Magelis when communicating to the Siemens S7-1200 ethernet driver?
Product Line:
S7-1211C, S7-1212C, S7-1214C, S7-1215C, S7 ethernet
Resolution:
Protection
From TIA (Siemens programming software), Select the CPU project in the left pane and press Alt-Enter (or in the contextual menu select “Properties…”)
In the item Protection, select “Full access” and Check “Permit access with PUT/GET communications from remote partner” as in figure below.
Information was taken from: http://snap7.sourceforge.net/snap7_client.html 2-25-2016
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.