How can we help you today?
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
My140CPU53414A is stuck in de-fragmentation mode. Is there any way to terminate this operation?
You will need to perform a power cycle on the CPU to terminate the operation.
This issue was fixed with the introduction of executive version 1.44E for CPUx341x. You should reflash the CPU to prevent this problem from re-appearing.
This issue was fixed with the introduction of executive version 1.44E for CPUx341x. You should reflash the CPU to prevent this problem from re-appearing.
Released for: Schneider Electric Vietnam
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.