What is the maximum customer cable size that can be connected per phase to ACB (MTZ/NT/NW) in BlokSeT?
In new BlokSeT catalogue, we have mentioned the maximum cable size that can be connected per phase of MTZ/NT/NW Masterpact. The cable includes both Copper and Aluminum cables.
For Example, for Side Connection, MTZ2/NW25 breaker, We can connect 2 x 300mm2 copper cables per phase.

For Example, for Side Connection, MTZ2/NW25 breaker, We can connect 2 x 300mm2 copper cables per phase.