You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
In some situations, the user may be interested in a specific current range that is different compared to the default value.
Please see the attached file for a detailed explanation of how to set up Schneider low-powered current transformers (LPCT) for use with Sepam relays.
AEDL3
Please see the attached file for a detailed explanation of how to set up Schneider low-powered current transformers (LPCT) for use with Sepam relays.
AEDL3
Released for: Schneider Electric Vietnam
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.