Steps to Activate Digital Output 2:
Based on the Command List, command to be send is 6003 to energize the output and command 6002 to de-energize.
Before sending the command be sure:
Unprotected Command Interface:
Based on the Command List, command to be send is 6003 to energize the output and command 6002 to de-energize.
Before sending the command be sure:
- The Digital Output is not assigned to an Alarm
- The Digital Output is configured to be controlled remotely/external
- Connect to the PM Meter with IP address of the Gateway and the unit ID
- READ ONLY ONCE REGISTER 405680 (5679)
- Value should be Unsigned integer different from 0
- Note this value (for example 12345)
- WRITE A BLOCK OF 3 REGISTERS STARTING ADDRESS 405000 (4999)
- Register 405000 (4999) should have Value 6003
- Register 405001 (5000) should have Value of the Semaphore (our example 12345)
- Register 405002 (5001) should have the ID of the Digital Output (2 for DO2)
- READ ONLY ONCE REGISTERS 405126 (5125) to confirm the result (should be 0 for Valid Operation)
Unprotected Command Interface:
- Connect to the PM Meter with IP address of the Gateway and the unit ID
- WRITE A BLOCK OF 3 REGISTERS STARTING ADDRESS 405250 (5249)
- Register 405250 (5249) should have Value 6003
- Register 405251 (5250) should have Value of 0
- Register 405252 (5251) should have the ID of the Digital Output (2 for DO2)
- READ ONLY ONCE REGISTERS 405376 (5375) to confirm the result (should be 0 for Valid Operation)