Issue:
ATV61 drive running fine and then changes to RDY status.
Product Line:
ATV61 Drives, Altivar 61
Environment:
Run Command
Cause:
n/a
Resolution:
The ATV61 was running ok and then went to RDY. Needs to check the run command. For 2-wire control. LI1 should have +24v. Can go to 1.2 and select I/O map, and check the status of LI1 or measure LI1 at the terminal card. If it drops low, they are loosing the run command.
Also, for 3-wire control or HMI control, a momentary loss of the safety circuit input on PWR will take status to RDY. Verify the factory jumper on +24-PWR or the safety circuit to PWR. Consider that a 24Vdc voltage sag would have same results. Check 24Vdc circuits for grounding.
ATV61 drive running fine and then changes to RDY status.
Product Line:
ATV61 Drives, Altivar 61
Environment:
Run Command
Cause:
n/a
Resolution:
The ATV61 was running ok and then went to RDY. Needs to check the run command. For 2-wire control. LI1 should have +24v. Can go to 1.2 and select I/O map, and check the status of LI1 or measure LI1 at the terminal card. If it drops low, they are loosing the run command.
Also, for 3-wire control or HMI control, a momentary loss of the safety circuit input on PWR will take status to RDY. Verify the factory jumper on +24-PWR or the safety circuit to PWR. Consider that a 24Vdc voltage sag would have same results. Check 24Vdc circuits for grounding.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.