Issue
In PME8.2 and previous versions
1. Too many registers exposed in Micrologic X driver (in this file only 66 measurements have been exposed similar to legacy Micrologic drivers)
2. IONReferenceName and MeasurementName attributes and not aligned MM_MeasurementMap and PDM labels respectively
Environment
EWS service
Resolution
1. Replace the Types.Measurements_MicrologicX file in C:\Program Files(x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\Extensions
2. Update the EWS server in Management console
In PME8.2 and previous versions
1. Too many registers exposed in Micrologic X driver (in this file only 66 measurements have been exposed similar to legacy Micrologic drivers)
2. IONReferenceName and MeasurementName attributes and not aligned MM_MeasurementMap and PDM labels respectively
Environment
EWS service
Resolution
1. Replace the Types.Measurements_MicrologicX file in C:\Program Files(x86)\Schneider Electric\Power Monitoring Expert\system\WebServices\Extensions
2. Update the EWS server in Management console