Issue:
Is it possible to program the ATV630 Process Drive Relay R2 for a 3 second delay before energizing
Product Line;
ATV630 ATV930
Environment:
All serial numbers
Cause:
Customer request.
Resolution:
Access: [Complete settings] [Input/Output] [Relay] [R2 configuration]
[R2 Delay time] r2d
R2 activation delay time has range 0...60,000 ms, so 3000 = 3 seconds.
The change in state takes effect once the configured time has elapsed, after the information becomes true.
The delay cannot be set for the [Operating State “Fault”] FLt assignment; and remains at 0.
Is it possible to program the ATV630 Process Drive Relay R2 for a 3 second delay before energizing
Product Line;
ATV630 ATV930
Environment:
All serial numbers
Cause:
Customer request.
Resolution:
Access: [Complete settings] [Input/Output] [Relay] [R2 configuration]
[R2 Delay time] r2d
R2 activation delay time has range 0...60,000 ms, so 3000 = 3 seconds.
The change in state takes effect once the configured time has elapsed, after the information becomes true.
The delay cannot be set for the [Operating State “Fault”] FLt assignment; and remains at 0.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.