Issue:
Cause of fault relay not changing state after the external fault is activated on the ATV630.
Product Line:
ATV630 and ATV930
Environment:
All
Cause:
The auto restart is preventing the relay from changing until the timeout is over.
Resolution:
The auto restart will prevent the fault relay from turning on until after the auto start time delay.