{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Can we use 220 V DC for RE22 or RE17 Relays

The maximum switching voltage for Re22 or RE17 is 110Vdc. At 110Vdc, the load current should be less than 0.3A.

Resistive Load: AC-1 8A, 250V conforming to IEC 60947-4-1
Inductive Load: DC-13 2A, 24V conforming to IEC 60947-5-1
Inductive Load: AC-15 3A, 250V conforming to IEC 60947-5-1

Schneider Electric Vietnam

Explore more
Range:
Harmony Electromechanical RelaysHarmony Control Relays
Explore more
Range:
Harmony Electromechanical RelaysHarmony Control Relays
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.