Issue:
ATS22 stops when the start button is released
Product Line:
MCC
Environment:
8639 22U
Cause:
ATS22 stops when the start button is released
Resolution:
Verify 2 wire / 3 wire control wiring configuration is correctly wired to the soft start.
Verify control circuit has no loose or open connections.
Verify RCR relay connections and operation.
Verify the latching circuit in the control wiring is being maintained to hold the run command.
ATS22 stops when the start button is released
Product Line:
MCC
Environment:
8639 22U
Cause:
ATS22 stops when the start button is released
Resolution:
Verify 2 wire / 3 wire control wiring configuration is correctly wired to the soft start.
Verify control circuit has no loose or open connections.
Verify RCR relay connections and operation.
Verify the latching circuit in the control wiring is being maintained to hold the run command.