Issue:
Use Network Protocol to control Relays and Digital Onputs on the ATV600/900 Drives.
Product Line:
Process ATV600 ATV900
Environment:
All models
Cause:
NA
Resolution:
Yes.
The relays ( R1 / R2 / R3... ) and digital outputs ( DQ1 / DQ2... ) can be controlled from the network by writing to address 5212. The relay or digital output assignment needs to be set to "Not Assigned". If it is assigned to a function, then the network write on the corresponding bit will not affect it. See the attached file.
Use Network Protocol to control Relays and Digital Onputs on the ATV600/900 Drives.
Product Line:
Process ATV600 ATV900
Environment:
All models
Cause:
NA
Resolution:
Yes.
The relays ( R1 / R2 / R3... ) and digital outputs ( DQ1 / DQ2... ) can be controlled from the network by writing to address 5212. The relay or digital output assignment needs to be set to "Not Assigned". If it is assigned to a function, then the network write on the corresponding bit will not affect it. See the attached file.
Released for: Schneider Electric Vietnam