How do you read run status on the ATV630 and ATV930 drives using profinet telegram 1?
Issue:
Read run status on ATV630 and ATV930 drives using profinet telegram 1.
Product Line:
Altivar ATV630 and ATV930 drive
Environment:
All
Cause:
Status word for run is bit 2
Resolution:
The second word in the input table on the profinet side is for status.
bit 2 is the enable or run operation.


Read run status on ATV630 and ATV930 drives using profinet telegram 1.