Issue
Within the PM8000 series meter modbus register list document there are three register present for minimum line to neutral THD, as shown below, but there are no equivalent registers for line-to-line values.
Min THD Voltage A-N 27,368
Min THD Voltage B-N 27,370
Min THD Voltage C-N 27,372
Product Line
PM8000 series
Environment
register list documentation
Resolution
Depending on the system type selected these three registers, 27,368, 27,370 and 27,372, read Min THD.
For WYE configuration these registers read Min THD Voltage L-N
For Delta configuration these registers read Min THD Voltage L-L