{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

What can cause a CANopen CoF fault on the ATV320 drive?

Issue:
ATV320 CANopen CoF fault

Product Line:
Altivar ATV320

Environment:
All

Cause:
Communication interruption on the CANopen® bus.

Resolution:
• Check the CANopen cables on the communication bus, check to see if there are 120 ohm line terminator resistors installed, check and verify baud rate setting parameter BDCO.
• Refer to the CANopen® User's manual: https://www.se.com/ww/en/download/document/NVE41309/

Module LED color & status description
-OFF No detected error reported Red single flash Detected error reported by the CANopen controller of the Altivar 320 (example: too many detected error frames)
-Red double flash Detected error due to the occurrence of a Node Guarding or a Heartbeat event
-Red ON The CANopen controller is in Bus OFF state

Schneider Electric Vietnam

Attachment(s)

ATV320_CANopen_Manual_EN_NVE41309_02.pdfATV320_CANopen_Manual_EN_NVE41309_02.pdf [1.38 MB]
Explore more
Category:
AC Drives and Soft Starters
Range:
Altivar Machine ATV320
Explore more
Category:
AC Drives and Soft Starters
Range:
Altivar Machine ATV320
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.