Issue:
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
Programming and understand skip frequency function of ATV630
Product Line:
ATV600
Environment:
All serial numbers
Cause:
Prevent prolonged operation within an adjustable range. Minimize noise at (x) frequency.
Resolution:
Jump frequency parameters can be located in Main Menu [Complete settings] -> [Generic Functions] -> [Jump frequency]
3 possible skip frequencies can be added at a time.
Skip frequency hysteresis is the frequency value range skipped.
For example, we have skip frequency value at 30 hz with hysteresis of 3hz. This means that the frequency range 27-33 will be skipped on ramp.
Released for: Schneider Electric Vietnam




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.