Question:
As for the X80 DDO module,
does ‘Supply Monitoring’ affect over current detect? i.e. If I uncheck ‘Supply Monitoring’ can I assume this channel will no longer trip on over current?
Answer:
No, supply monitoring is only used for supervising the threshold voltage of Pre-actuator. In case it does not exceed the threshold voltage, the output will be off.
The channel over current will be always indicated via LED
As for the X80 DDO module,
does ‘Supply Monitoring’ affect over current detect? i.e. If I uncheck ‘Supply Monitoring’ can I assume this channel will no longer trip on over current?
Answer:
No, supply monitoring is only used for supervising the threshold voltage of Pre-actuator. In case it does not exceed the threshold voltage, the output will be off.
The channel over current will be always indicated via LED