You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
AC control power - PM2125
Operating range 80 - 277 V L-N ± 10%
Burden < 8 VA at 277 V L-N
Frequency range 45 - 65 Hz
Ride-through time 100 ms typical at 120 V AC and maximum burden
400 ms typical at 230 V AC and maximum burden
DC control power - PM2125
Operating range 100 - 277 V DC ± 10%
Burden < 3.3 W at 277 V DC
Ride-through time 50 ms typical at 125 V DC and maximum burden
Operating range 80 - 277 V L-N ± 10%
Burden < 8 VA at 277 V L-N
Frequency range 45 - 65 Hz
Ride-through time 100 ms typical at 120 V AC and maximum burden
400 ms typical at 230 V AC and maximum burden
DC control power - PM2125
Operating range 100 - 277 V DC ± 10%
Burden < 3.3 W at 277 V DC
Ride-through time 50 ms typical at 125 V DC and maximum burden