Issue:
Why is ATV340 experiencing CRF fault on his Process drive.
Product Line:
ATV340
Environment:
All ATV340
Cause:
Charging circuit control detected error or charging resistor damaged.
Resolution:
Why is ATV340 experiencing CRF fault on his Process drive.
Product Line:
ATV340
Environment:
All ATV340
Cause:
Charging circuit control detected error or charging resistor damaged.
Resolution:
- Turn off the drive, wait for the display to turn off, then wait 15 more seconds and turn on again.
- Verify the internal connections.
- Contact your local Schneider Electric representative