The UL 1053 standard defines in Table 22.1 the operating time of the ground fault protection devices:
Ground-fault current (A) | Time (s) |
85% of pickup current | Shall not trip |
115% of pickup current | Ultimately |
150% of pickup current | 2 |
250% of pickup current | 1 |