{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
PME 9.0 - Cannot deactivate alarms in Management Console if logged in as a non-admin domain Windows users

Issue
Try to use Management Console's "Deactivate Alarms" feature, as a non-admin user, to deactivate one or more of those active alarms and the following error will appear:

"an unexpected condition was encountered while initializing the AlarmInactivator: Write to Primary data queue failed.."



Product Line

Power Monitoring Expert 9.0

Envorinment
Management Console -  "Deactivate Alarm" feature

Cause
PME's MQ setup uses the "Everyone" bucket for permissions and permissions set for the "Everyone" group DO NOT APPLY to domain users by default.

Resolution

Resolution 1:
Run Management Console "As Administrator" (i.e. the right-click menu in Windows).

Resolution 2:
1. Log in as administrator of the server
2. Open the Windows Start menu and search "Computer Management"
3. Open Computer Management then expand Services and Applications > Message Queues
4. Check permissions for all of the private queues by right-clicking on each of them and selecting Properties > Security
  • List of private queues to check:
    • cloudagent_control
    • cloudagent_data
    • logsubsystemprimaryrouter_control
    • logsubsystemprimaryrouter_data
    • logsubsystemsecondaryrouter_control
    • logsubsystemsecondaryrouter_data
  • Make sure each of the queues listed above have the following permissions:
    • "Everyone" group has access to allow:
      • Get Properties
      • Get Permissions
      • Send Message
    • "Administrators" group should have full access to the queue
    • "ANONYMOUS LOGON" Group should only have access to:
      • Send Message
5. If the issue persists (and using Windows domain account), add the domain group to the security tab and allow permissions to:
  • Get Properties
  • Get Permissions
  • Send Message
6. Restart "Message Queuing" service in Services

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: