{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What causes 'Unknown Error' when building a Unity Pro/Control Expert project?
The original project (non-Unity) may have an empty DIO drop.
If so, delete this drop before inporting the project
or after importing the project, delete the empty DIO drop in the Unity Pro/Control Expert project.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: