{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.

Modicon M221 - TM3 bus doesn’t work with TM3DM24R or TM3XTYS4 SV 2.0

  • Problem description:
If TM3DM24R or TM3XTYS4 module is placed before TM3 analog input modules (TM3A* or TM3T*) with TM221 controller.
  • Results:
- The TM3 expansion bus communication is not operationnal, the IO ERR Led is fixed red.
- The system word %SW118 is different than 16#FFFF (bit 13 or bit 14 is set to 0).

=> This issue is fixed by the M221 firmware version v1.10.1.3 attached to this FAQ.
  • How to update M221 with .mfw file:
See attached document.

Schneider Electric Vietnam

Attachment(s)

M221 - FW V1.10.1.3.zipM221 - FW V1.10.1.3.zip [429.2 KB]
How to update M221 with .mfw file.docx.zipHow to update M221 with .mfw file.docx.zip [126.12 KB]
Explore more
Range:
Modicon M221Modicon TM3
Explore more
Range:
Modicon M221Modicon TM3
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.