Issue 
When using the Generator Performance Configuration Tool to auto generate EPSS diagram in Vista and using ATS parameters, the link to the the ATS load data register is missing, therefore no value for this parameter. 
ATS rating is linked but not the ATS load data.  
Product Line 
Power Monitoring Expert 8.x, 9.0 and 2020 
Enviroment 
EPSS Vista Diagram 
Cause 
Automatic linking to the register is missing 
Resolution 
Manually link the register in Vista to the ATS Load Data 
1) Open the EPSS - ATS diagram in Vista 
2) Go to Option > Show Toolbox 
3) Right click on the box where the value were supposed to appear 
4) Link > Custom > Edit Link 
5) Select the correspondent source and measurement 
Released for: Schneider Electric Vietnam