Can we put several coils in parallel in the middle of one ladder line and place contacts after them?
EcoStruxure Control Expert / Any Unity Version Although inserting a contact after coils is not recommended a per PLC Open IEC 61131 programming guiding rule 6.3.1, it is supported when you untick the “Right-justify coils” in the option.
But be aware to prevent short cutting the top line of the parallel coils, which in consequence might give rise to the unexpected logic results on the coils to the end.
The proper way is to remove the short circuit on top line of the parallel coils to make the logic execution consistently.
EcoStruxure Control Expert / Any Unity Version Although inserting a contact after coils is not recommended a per PLC Open IEC 61131 programming guiding rule 6.3.1, it is supported when you untick the “Right-justify coils” in the option.
But be aware to prevent short cutting the top line of the parallel coils, which in consequence might give rise to the unexpected logic results on the coils to the end.
The proper way is to remove the short circuit on top line of the parallel coils to make the logic execution consistently.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.