Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Can you power the Altivar 212 drive using the DC bus?
Issue:
Is there a way to use the ATV212 drives with a Bonitron DC power supply for a site that only has single phase available?

Product line:
Altivar Building ATV212 Altivar 212

Cause:
Application single phase supply

Resolution:
The ATV212 are not suitable to be powered with single phase or by the DC bus.  The DC power terminals are present on the drives; however, they're covered with glue to prevent connection.  The DC bus terminals can only be used for measuring the DC bus.

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings