Issue:
When will a Solid State Overload trip when there is current Imbalance
Product Line:
NEMA and Definite Purpose Contactors and Starter
Environment:
9065 Solid State Overload Relay
Resolution:
The unit is guaranteed to trip within 3 seconds at 25% phase current imbalance. It will start tripping at +/- 17% imbalance.