EPS UPSs or SSC with GUI that the touch point is off
Public
Issue:
EPS UPSs or SSC with GUI that the touch point is off
Product line:
All EPS UPSs or SSC with GUI
Environment:
All EPS UPSs or SSC with GUI
Cause:
The touch point is off on the GUI and needs to be calibrated to reset touch point.
Resolution:
How to calibrate the GUI:
1. Click on Start->Settings->Control Panel->Stylus->Calibration->Recalibrate.
2. Calibrate the five point accurately.
3. Press ENTER if keyboard is connected else TAP on the screen, it will exit the calibration screen.
4. Save registry from Start->Programs->ColibriTools->SaveReg.
Issue:
EPS UPSs or SSC with GUI that the touch point is off
Product line:
All EPS UPSs or SSC with GUI
Environment:
All EPS UPSs or SSC with GUI
Cause:
The touch point is off on the GUI and needs to be calibrated to reset touch point.
Resolution:
How to calibrate the GUI:
1. Click on Start->Settings->Control Panel->Stylus->Calibration->Recalibrate.
2. Calibrate the five point accurately.
3. Press ENTER if keyboard is connected else TAP on the screen, it will exit the calibration screen.
4. Save registry from Start->Programs->ColibriTools->SaveReg.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.