What is an SOF fault on the ATV12?

Article available in these languages: Spanish

Issue:
SOF fault on ATV320

Product Line:
Altivar Machine, ATV12

Environment:
All serial numbers

Cause:
• Instability
• Overspeed associated with the inertia of the application

Resolution:
• Check the motor
• Overspeed is 10% more than Maximum frequency tFr page 57 so adjust this parameter if necessary
• Add a braking resistor
• Check the size of the motor/drive/load
• Check parameters of the speed loop (gain and stability)

ATV user manual: