Why can't I open my .STU file but .STA works using CE V15.0 ?
Issue
When upgrading a Control Expert project created with a version earlier than V14.1 to Control Expert V15, an issue may occur if the project contains password-protected elements.
The issue may be related to one of the following configurations:
- Password protection is configured without a password.
- Password protection is configured with an empty password.
These configurations are no longer allowed in Control Expert V15 and later.
Product Line
EcoStruxure Control Expert
Environment
- Project originally created with a Control Expert version earlier than V14.1
- Project opened or upgraded with Control Expert V15
Resolution
Two possible resolutions are currently identified:
Option 1: Upgrade Control Expert
Upgrade to Control Expert V15.1, where this issue is reported as corrected.
Option 2: Remain on Control Expert V15
If Control Expert V15 must be retained:
- Export the affected DFBs.
- Reimport the DFBs into the project.
- Verify that the project can then be processed without the password-related issue.