Why are the OPC UA client values not updating when using the UA_ReadList function block?
Changing the value type of the OPC UA client may prevent the client values from updating.
Performing the following steps may resolve the issue:
Performing the following steps may resolve the issue:
- Export the project as a .ZEF file
- Import the .ZEF file
- Run a Rebuild All project
- Download Project to controller