What is an INF27 (internal error 27) on an ATV630 drive?
Principle:The selftest of the internal CPLD has detected an error.
Probable cause:Internal CPLD error
Remedies:
  • Remove any existing connections made on the VFD 24V supply terminal. Power cycle VFD. If applicable, update firmware of the VFD to the latest version.
Possible causes
  • The communication cable connected to the Modbus port, or any other fieldbus port has been damaged (Example: Modbus Cable to the HMI or door mounting kit) - Disconnect the cable and check if the error disappears.

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings