You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
PowerChute Network Shutdown version 5 reports, "Could not connect to the vCenter Server over the network."

Product:
PowerChute Network Shutdown version 5
Environment:
VMware vCenter Server 7.x or 8.x
Cause:
Misconfiguration
Solution:
See the attached PDF
How to troubleshoot Cannot connect to vCenter Server.pdf
PowerChute Network Shutdown version 5 reports, "Could not connect to the vCenter Server over the network."
Product:
PowerChute Network Shutdown version 5
Environment:
VMware vCenter Server 7.x or 8.x
Cause:
Misconfiguration
Solution:
See the attached PDF
How to troubleshoot Cannot connect to vCenter Server.pdf
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.