Issue:
SL subfeed lug kit for I-Line
Product Line:
I-Line panelboard
Environment:
SL sub feed kit
Cause:
Technical reason for the sub feed lug kit to be be equal to or greater that the ampacity of the interior.
Resolution:
The reason is due to not having an over current protection device between the bus and the wires attached to the SL sub-feed kit. Consider a 1200A I-Line interior and a SL400 sub-feed lug kit. The wires would only be rated at 400A but attached to 1200A with nothing to protect them from overcurrent. A breaker would be different since it is an over current device.
SL subfeed lug kit for I-Line
Product Line:
I-Line panelboard
Environment:
SL sub feed kit
Cause:
Technical reason for the sub feed lug kit to be be equal to or greater that the ampacity of the interior.
Resolution:
The reason is due to not having an over current protection device between the bus and the wires attached to the SL sub-feed kit. Consider a 1200A I-Line interior and a SL400 sub-feed lug kit. The wires would only be rated at 400A but attached to 1200A with nothing to protect them from overcurrent. A breaker would be different since it is an over current device.
Released for: Schneider Electric Vietnam
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.