- Press NEXT three times and CALIB will be displayed
- Press ENTER and CAL ATO will be displayed
- Press Next and CAL LRV will be displayed
- Apply the lower range value pressure to the transmitter
- Press ENTER and CALWAIT will be displayed
- After 10-15 seconds, LRVdone will be displayed
- Press NEXT and CAL URV will be displayed
- Apply the upper range value pressure to the transmitter
- Press ENTER and CALWAIT will be displayed
- After 10-15 seconds, URVdone will be displayed
- Press NEXT until SAVE is displayed
- Press ENTER
- Complete