How to read timestamped input of a BMXERT1604 module ?

Issue:

How to retrieve the timestamp of an input located in a BMXERT1604T module

Product Line:

BMXERT1604, M580 CPU

Environment:

EcoStruxure Control Expert V16.2, Windows 10

Resolution:

The GET_TS_EVT_M function block gets the time stamped data in:

  • BMX ERT 1604T when located in Modicon M340 local drop

  • BMX ERT 1604T when located in Modicon M580 local and remote drops

  • BME P58 Modicon M580 controller

  • BMX CRA 312 10 of a Modicon M580

  • BME CRA 312 10 of a Modicon M580

This function allows reading the event buffer to make it available for the controller application:

Screenshot1

To launch the communication function only once, the ENABLE signal needs to be reset to 0 after the ACTIVE parameter is set to 0. If the ENABLE parameter is maintained to 1 after the ACTIVE parameter is set to 0, the communication function is launched again and the ACTIVE parameter is set to 1 on the next cycle.

If the ENABLE bit is reset to 0 before completion, the function block is stopped (active bit to 0). To have a complete block execution, the value of 1 must be applied on the ENABLE bit until the operation has finished or until an error has occurred.

Screenshot2

  • The ADR pin must be connected to an ADDMX or ADDM function.
  • The BUFFER array will contain the event timestamp entries, retrieved from the BMXERT1604 module.

Attached a description of the GET_TS_EVT_M function

To configure the BMXERT1604 on an M580, please follow this video : Video: How to configure a BMXERT1604 Timestamp module in an M580 application | Schneider Electric Belgium

Schneider Electric Vietnam

Attachment(s)
GET_TS_EVT_M description.pdf [394.82 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings