What can trigger a bUF or braking unit resistor short circuit fault on the ATV930 Process drives?

Article available in these languages: Spanish

Issue:
Getting a bUF or braking unit resistor short circuit fault on the ATV930 Process drives.

Product Line:
Altivar Machines,  Altivar 930

Cause:
Short circuit inside the braking module
Braking resistor is shorted out
Short circuit to ground
BRA=No ( ramp auto adaptation) and no DB resistor

Resolution:
Check the braking units wiring and the resistor connections
Check the drives configurations

NOTE: ATV630 drives do not accept DB resistor connections.