Issue:
Relay and Analog Output not working on ATV630.
Product Line:
ATV630
Environment:
Output Phase Loss
Cause:
n/a
Resolution:
First check all the relay and analog output settings in menu 5.11.
Go to 5.12 ( Error/Warning handling) and scroll down to Output Phase loss- if you want to turn off the Output Phase Loss, set to Function Inactive ( DO NOT SET to No Error Triggered).
Relay and Analog Output not working on ATV630.
Product Line:
ATV630
Environment:
Output Phase Loss
Cause:
n/a
Resolution:
First check all the relay and analog output settings in menu 5.11.
Go to 5.12 ( Error/Warning handling) and scroll down to Output Phase loss- if you want to turn off the Output Phase Loss, set to Function Inactive ( DO NOT SET to No Error Triggered).
Released for:Schneider Electric Global

