Product FAQs

Ask a Question

How do I program an ATV630 relay r2 for a 3 second delay before energizing?

Issue:
How do I program an ATV630 relay r2 for a 3 second delay before energizing?

Product Line; 
ATV630

Environment
All serial numbers 

Cause
Customer request. 

Resolution
Access  
[Complete settings] [Input/Output] [Relay] [R2 configuration]
Identical to [R2 configuration]   r2 
[R1 Delay time] r2d
R2 activation delay time.     range    0...60,000 ms     3000 = 3 seconds 
The change in state takes effect once the configured time has elapsed when the information becomes true.
The delay cannot be set for the [Operating State “Fault”] FLt assignment; and remains at 0.
Was this helpful?
What can we do to improve the information ?