What are the standard rated voltages for medium voltage fuse according to IEC 60282-1? How to properly define its value?
A voltage used in the designation of the fuse-base or fuse-link, from which the test conditions are determined.
The rated voltage of a fuse and should be selected from the following table:


Notes:
  • This rated voltage represents the highest voltage for the equipment,
  • On three-phase solidly earthed systems, fuses may only be used provided that the highest system voltage is less than or equal to their rated voltage.
  • On single phase or non-solidly earthed systems, fuses may only be used provided that the highest system voltage is less than or equal to 87 % of their rated voltage, unless specific testing has been performed