RE17RMMWS Product picture Schneider Electric

Range: Zelio Time

Relay Output

RE17RMMWS

RE17RMMWS Product picture Schneider Electric
Range: Zelio Time

Relay Output

RE17RMMWS

time delay relay 10 functions - 1 s..100 h - 12..240 V AC/DC - 1 OC

Show more characteristics >
Add to My Products Remove from My Products

  • Main
    range of product
    Zelio Time
    product or component type
    Modular timing relay
    discrete output type
    Relay
    width
    17.5 mm
    device short name
    RE17R
    time delay type
    A
    Ac
    At
    B
    Bw
    C
    D
    Di
    H
    Ht
    time delay range
    0.1...1 s
    1...10 h
    1...10 min
    1...10 s
    10...100 h
    6...60 min
    6...60 s
    nominal output current
    8 A
    Complementary
    contacts type and composition
    1 C/O
    contacts material
    Cadmium free
    control type
    Selector switch on front panel
    [Us] rated supply voltage
    12...240 V AC/DC at 50/60 Hz
    voltage range
    0.85...1.1 Us
    supply frequency
    50...60 Hz (+/- 5 %)
    release of input voltage
    5 V
    connections - terminals
    Spring terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 (solid) without cable end
    Spring terminals, clamping capacity: 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16 (flexible) with cable end
    tightening torque
    0.6...1 N.m conforming to IEC 60947-1
    housing material
    Self-extinguishing
    repeat accuracy
    +/- 0.5 % conforming to IEC 61812-1
    temperature drift
    +/- 0.05 %/°C
    voltage drift
    +/- 0.2 %/V
    setting accuracy of time delay
    +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
    control signal pulse width
    100 ms with load in parallel typical
    30 ms typical
    insulation resistance
    100 MOhm at 500 V DC conforming to IEC 60664-1
    reset time
    120 ms on de-energisation typical
    on-load factor
    100 %
    power consumption in VA
    0...3 VA at 240 V AC
    power consumption in W
    <= 1.5 W at 240 V DC
    minimum switching current
    10 mA at 5 V DC
    maximum switching current
    8 A AC/DC
    maximum switching voltage
    250 V AC
    breaking capacity
    <= 2000 VA
    operating frequency
    10 Hz
    electrical durability
    100000 cycles for resistive load (8 A at 250 V AC maximum)
    mechanical durability
    10000000 cycles
    dielectric strength
    2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
    [Uimp] rated impulse withstand voltage
    5 kV (1.2/50 µs)
    power on delay
    < 100 ms
    marking
    CE
    creepage distance
    4 kV/3 conforming to IEC 60664-1
    safety reliability data
    MTTFd = 296.8 years
    B10d = 270000
    mounting position
    Any position in relation to normal vertical mounting plane
    mounting support
    35 mm DIN rail conforming to EN/IEC 60715
    local signalling
    LED indicator on steady: relay energised, no timing in progress
    LED indicator flashing: timing in progress (80 % ON and 20 % OFF)
    LED indicator pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) (5 % ON and 95 % OFF)
    product weight
    0.07 kg
    Environment
    immunity to microbreaks
    <= 20 ms
    standards
    2004/108/EC
    EN 61000-6-1
    EN 61000-6-2
    EN 61000-6-3
    EN 61000-6-4
    IEC 61812-1
    2006/95/EC
    product certifications
    CSA
    cULus
    GL
    ambient air temperature for storage
    -30...60 °C
    ambient air temperature for operation
    -20...60 °C
    IP degree of protection
    IP20 (terminal block) conforming to IEC 60529
    IP40 (housing) conforming to IEC 60529
    IP50 (front panel) conforming to IEC 60529
    vibration resistance
    20 m/s² (f = 10...150 Hz) conforming to IEC 60068-2-6
    shock resistance
    15 gn (duration = 11 ms) conforming to IEC 60068-2-27
    relative humidity
    93 % without condensation conforming to IEC 60068-2-30
    electromagnetic compatibility
    Electrostatic discharge immunity test, in contact at 6 kV conforming to IEC 61000-4-2 level 3
    Electrostatic discharge immunity test, in air at 8 kV conforming to IEC 61000-4-2 level 3
    Susceptibility to electromagnetic fields, 80 MHz to 1 GHz at 10 V/m conforming to IEC 61000-4-3 level 3
    Electrical fast transient/burst immunity test, capacitive connecting clip at 1 kV conforming to IEC 61000-4-4 level 3
    Electrical fast transient/burst immunity test, direct at 2 kV conforming to IEC 61000-4-4 level 3
    1.2/50 µs shock waves immunity test, differential mode at 1 kV conforming to IEC 61000-4-5 level 3
    1.2/50 µs shock waves immunity test, common mode at 2 kV conforming to IEC 61000-4-5 level 3
    Conducted RF disturbances, 0.15...80 MHz at 10 V conforming to IEC 61000-4-6 level 3
    Voltage dips and interruptions immunity test, 1 cycle at 0 % conforming to IEC 61000-4-11
    Voltage dips and interruptions immunity test, 25/30 cycles at 70 % conforming to IEC 61000-4-11
    Conducted and radiated emissions conforming to EN 55022 class B
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    RoHS (date code: YYWW)
    REACh
    Product environmental profile
    Product end of life instructions
    Available
  • Documents and Downloads

    Language
    • English
    Catalogue
    Date
    Size
    Add to My Documents
    Date 2018/04/30
    Size 7.7 MB
    Certificate
    Date
    Size
    Add to My Documents
    UL Listed RE17, RE22, REXL, RE48A, RE88857, RE88865, RE88867, RENF22R2MMW
    Instruction sheet
    Date
    Size
    Add to My Documents
    Declaration of conformity
    Date
    Size
    Add to My Documents
    Date 2018/08/06
    Size 242.8 KB
    End of life manual
    Date
    Size
    Add to My Documents
    Date 2017/12/13
    Size 1.4 MB
  • Technical FAQs

    No results found
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.
  • Dimensions Drawings

    Width 17.5 mm



  • Connections and Schema

    Internal Wiring Diagram



    Wiring Diagram


    1) Contact Y1:

    • Control for functions B, C, Ac, Bw, Ad, Ah, N, O, W, T, Tt.

    • Partial stop for functions At, Ht and Pt.

    • Function D if Di selected.

    • Not used for functions A, H and P.


  • Technical Description

    Function A : Power on Delay Relay
    Description

    The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function Ac : On- and Off-Delay Relay with Control Signal
    Description

    After power-up, closing of the control contact C causes the timing period T to start (timing can be interrupted by operating the Gate control contact G). At the end of this timing period, the relay closes.

    When control contact C re-opens, the timing T starts.

    At the end of this timing period T, the output reverts to its initial position (timing can be interrupted by operating the Gate control contact G).

    The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function At : Power on Delay Relay (Summation) with Control Signal
    Description

    After power-up, the first opening of control contact C starts the timing. Timing can be interrupted each time control contact closes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output relay closes.

    Function: 1 Output


    T = t1 + t2 +...


    Function B : Interval Relay with Control Signal
    Description

    After power-up, pulsing or maintaining control contact C starts the timing T. The output R closes for the duration of the timing period T then reverts to its initial state.

    Function: 1 Output



    Function Bw : Double Interval Relay with Control Signal
    Description

    On closing and opening of control contact C, the output R closes for the duration of the timing period T.

    Function: 1 Output



    Function C : Off-Delay Relay with Control Signal
    Description

    After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function D : Symmetrical Flasher Relay (Starting Pulse Off)
    Description

    Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T.

    The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function Di : Symmetrical Flasher Relay (Starting Pulse On)
    Description

    Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T.

    The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function H : Interval Relay
    Description

    On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous.

    Function: 1 Output


    Function: 2 Outputs


    2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)


    Function Ht : Interval Relay (Summation) with Control Signal
    Description

    On energisation, the output R closes for the duration of a timing period T then reverts to its initial state.

    Pulsing or maintaining control contact C will again close the output R.

    Timing T is only active when control contact C is released and so the output R will not revert to its initial state until after a time t1 + t2 +...

    The relay memorises the total, cumulative opening time of control contact C and, once the set time T is reached, the output R reverts to its initial state.

    Function: 1 Output


    T = t1 + t2 +...


    Legend

    Relay de-energised

    Relay energised

    Output open

    Output closed

    C

    Control contact

    G

    Gate

    R

    Relay or solid state output

    R1/R2

    2 timed outputs

    R2 inst.

    The second output is instantaneous if the right position is selected

    T

    Timing period

    Ta -

    Adjustable On-delay

    Tr -

    Adjustable Off-delay

    U

    Supply