May inputs on a MiCOM Px20 relay be assigned to outputs?

Issue

Users need to know whether digital inputs on a MiCOM Px20 relay can be directly linked or assigned to output contacts for control or tripping purposes.

Product

MiCOM Px20

Environment

Protection relay configuration and automation control settings within MiCOM Px20 relays.

Cause

Uncertainty in configuring the relay logic to allow digital inputs to drive output contacts or initiate tripping functions.

Resolution

Yes, the inputs can be assigned to outputs. Inputs may be directly linked to a trip contact or assigned through intermediary logic such as a 52A/52B breaker status contact and programmed accordingly.

To configure this:

  • Navigate to the Automation Control section in the relay settings.
  • Locate the Inputs configuration submenu.
  • Assign the desired input signals to the corresponding outputs or logic functions as required.

Example of 52A and 52B in Px2x connected to inputs

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Conditions générales d'affaires
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings