How is the ATV212 set for HMI controls for both RUN/STOP and speed reference?

Issue:
How is the ATV212 set for HMI controls for both RUN/STOP and speed reference?

Product Line:
Altivar 212

Environment:
All models

Cause:
Control for VFD to be from the HMI

Resolution:
There are several options.
1) Put the VFD in Local Mode by pressing the LOC/REM button on the integral keypad, or the F4 button on the remote keypad.  Indicators for Local Mode are the green LED is ON for LOC/REM, or LOC is displayed above the F1 button.
2) Keep the VFD in Remote Mode and set CMOd=1 and FMOd=3

Both of these options apply for integral keypad or remote keypad control.

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

Hulp nodig?

Selecteer zelf het juiste product

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings