Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
		
Hoe kunnen wij u vandaag helpen?
Can I automatically backup my Alarm Summary page in Vijeo Designer?

Yes. In Vijeo-Designer, the alarm information (from all 3 types of alarm databases: Active, History and Log) can be backed up to the SRAM so that it is not lost when a power outage occurs. To do this, click "Alarms" in the Navigator and set the "Backup Alarm Group" property to "Yes".
image1


image2

When Backup Alarm Group = Yes in the Alarms node properties, the Num Of History Alarms and Num Of Log Alarms in the alarm group properties, plus the number of variable alarms, define how many alarms are backed up to SRAM.
Backup Alarms = History + Log + Active

Schneider Electric Belgium

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Schneider Electric Community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings