Quick start for configuring the TCSEGDB23F24FA M340 Modbus Plus Proxy Module.

Issue

Quick start for configuring the 'TCSEGDB23F24FA' M340 Modbus Plus Proxy Module

Product Line
'TCSEGDB23F24FA' M340 Modbus Plus Proxy Module

Environment
Windows 7

Resolution
The following steps can be used to configure the' TCSEGDB23F24FA' M340 Modbus Plus Proxy
Module

  • Set the Modbus Plus address for the bridge using the rotary switch that are located on the back
of the module.
  • Connect to the module using the default MAC derived ethernet address.
  • Enter the default username (USER) and password (USER) to access the configuration/setup
web pages.
  • Click on 'Setup'.
  • Click on 'IP Setup'.
  • Enter the IP address parameters.
  • Click on 'Apply'.
  • Click on 'Save To Flash'.
  • Click on 'IP address' under the section labeled 'M340 Interface'.
  • Enter the IP address parameters.
  • Click on 'Apply'.
  • Click on 'Save To Flash'.
  • Click on 'Register Offsets' under the 'M340 Interface' section.
  • Fill in the appropriate parameters.
  • Select 'Legacy Compatability 0x 4x by 1' if you are communicating to a Modicon PLC.
  • Click on 'Apply'.
  • Click on 'Save To Flash'.
  • If applicable, click on the appropriate sections to be filled in under the section named 'Modbus Plus Peer Cop'

Schneider Electric Belgium

Ontdek meer

Hulp nodig?

Selecteer zelf het juiste product

Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

Offerte aanvragen

Dien uw aanvraag online in en een expert zal contact met u opnemen.

Verkooppunten

Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

Help Center

Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.