Why we are not able to fix LADN01 & LADN10 auxiliary contact on LC1D09 / LC1D25 contactor?

Article available in these languages: Turks

Yes, you will not be able to fix one contact auxiliary (LADN10 & LADN01) in contactors from LC1D09 to LC1D38. You will be able to fix only 2 contacts auxiliary (LADN20, LADN02 etc..) and 4 contacts auxiliary (LADN22, LADN13 etc..). This information is already mentioned in the catalog.

The specific information is highlighted in catalog page extract attached herewith for your reference.
You can refer (1) maximum number of auxiliary contacts that can be fitted: It is mentioned that "1 contact = (-)", it means you can not fix 1 contact auxiliary in LC1D09 to LC1D38.

Schneider Electric Belgium

bijlage(n)
Tesys D - Auxillary contact fixing.pdf [253.22 KB]
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie

Hulp nodig?

  • Selecteer zelf het juiste product

    Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.

  • Offerte aanvragen

    Dien uw aanvraag online in en een expert zal contact met u opnemen.

  • Verkooppunten

    Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.

  • Help Center

    Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.

  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Vind onze kantoren
  • Offerte aanvragen?
  • Verkooppunten
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Privacybeleid
  • Cookieverklaring
  • Gebruiksvoorwaarden
  • Algemene verkoop- en inkoopvoorwaarden
  • Change your cookie settings