Issue:
Troubleshooting an SCF3 fault on an Altivar Process Drive.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All products of Altivar Process Drive
Cause:
N/A
Resolution:
Description
SCF3 - Ground Short Circuit Fault
Earth fault at the output
Possible causes
Troubleshooting an SCF3 fault on an Altivar Process Drive.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All products of Altivar Process Drive
Cause:
N/A
Resolution:
Description
SCF3 - Ground Short Circuit Fault
Earth fault at the output
Possible causes
- Short circuit or earth fault at the inverter output.
- Short circuit on a motor with long cables.
- Insulation fault in the motor or in the cables.
- Perform Diagnostic Test
- IGBT or Transistor Test
- Check the cables connecting the drive to the motor and the motor insulation.
- Megger motor from cables. Use at least 1000v
- Check for proper grounding
- Check distance between drive and motor
- Over 165 ft may require the use of a load reactor or filter
- Check Switching Frequency
- Lower it if possible
Gepubliceerd voor: Schneider Electric Belgium




Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.