Hoe kunnen wij u vandaag helpen?
Why Can I Connect to the Modicon Edge I/O NTS but Cannot Download a Configuration?
This behavior is typically caused by a version compatibility mismatch between the Modicon Edge I/O firmware and the Edge I/O Configurator version being used.
In Control Expert v16.2, the integrated Edge I/O Configurator is based on an older version. As a result, if the Network Interface Module (NIM) firmware has been upgraded to a newer revision, you may still be able to:
- Connect to the Edge I/O system
- View and monitor device status
- Access diagnostic information
However, downloading a new configuration to the NIM is not supported because the older configurator version does not fully support the newer firmware.
This limitation has been highlighted in the Modicon Edge I/O NTS Modicon Edge I/O Configurator Release Notes, page 19.
Gepubliceerd voor: Schneider Electric Belgium
Ontdek meer
Product:
Ontdek meer
Product:
Hulp nodig?
Selecteer zelf het juiste product
Vind snel en eenvoudig de juiste producten en toebehoren voor uw toepassingen.
Offerte aanvragen
Dien uw aanvraag online in en een expert zal contact met u opnemen.
Verkooppunten
Vind eenvoudig de dichtstbijzijnde distributeur van Schneider Electric op uw locatie.
Help Center
Vind de antwoorden die u nodig heeft via bladeren door veelgestelde vragen over onderwerpen.