Can the ground fault function be defeated for primary injection testing on Masterpact NT breakers?
Issue:
Is there a way to defeat ground fault on the Masterpact NT breakers in order to perform primary injection testing?
Product Line:
Circuit Breakers
Resolution:
There are three ways to defeat ground fault on the NT breaker. The hand held and full function test kits can both be used to defeat ground fault. If neither of these devices are available, the "looping method" will have to be employed for primary injection testing. In this method, jumpers are added line and load so that each pole may be tested separately. The below drawing shows looping when testing A phase. For B and C phases, move jumpers as necessary.
Is there a way to defeat ground fault on the Masterpact NT breakers in order to perform primary injection testing?
Product Line:
Circuit Breakers
Resolution:
There are three ways to defeat ground fault on the NT breaker. The hand held and full function test kits can both be used to defeat ground fault. If neither of these devices are available, the "looping method" will have to be employed for primary injection testing. In this method, jumpers are added line and load so that each pole may be tested separately. The below drawing shows looping when testing A phase. For B and C phases, move jumpers as necessary.
Released for: Schneider Electric Canada


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.